Elspec is a leading global provider of advanced power quality analyzers, power quality solutions and power monitoring software. We focus on developing technology that shifts the power quality market to the next level. With over 45 years of experience, we develop tailor-made power quality solutions along with state of the art power quality analyzers.
The BlackBox G4500 portable takes power quality analyzers & power monitoring to a whole new level by using the revolutionary PQZIP patent algorithm. The unique algorithm Enables you to measure, store & analyze (continuously) waveform signals regardless their size
Trigger free setup
5,000 power parameters @ 1/2 cycle resolution
Easy deployment

The G4500 portable power quality analyzer is able to record and store all electrical waveform continuously for more than a year, with no gaps in the data. The G4500 portable power quality analyzer offers a clear and comprehensive picture of the conditions before, during, and after an event.
The G4500 portable power quality meter measures and records 5,000 power parameters continuously at a resolution of ½ cycles, 10/12 cycles, 150/180 cycles, 10 min and 2 hours of which, any given resolution is calculated for display and reporting purposes. Hence, there is no need to select which parameters to log, and more importantly, which parameters to ignore.


The G4500 portable power quality analyzer has two FFT engines for harmonics analysis: Cycle by Cycle: performs FFT at 1 cycle resolution for extended bandwidth. This engine provides 512 harmonics order at 50Hz resolution. 10/12 Cycles: performs FFT 10/12 cycles resolution for extended resolution and sub-grouping calculation. This engine provides the magnitude and angle of 512 spectrum components at 5Hz resolution.
The G4500 portable power quality meter is designed to detect any event occurring on your system. The mechanism allows you to configure events on any measured parameter (more than 1,000) and/or I/O ports. The event mechanism supports out-of-limit events as well as rate of changed limits. The G4500 analyzer is capable of recording waveform signals continuously. The event configuration doesn’t trigger the recording but rather stores summary logs including start and end time, duration, severity and magnitude of the event. All events can be displayed in a tabular or scatter charts as CBEME/ITIC.

Waveform Sampling | |
|---|---|
| Voltage Sampling Rate | 1024 Samples/Cycle |
| Current Sampling Rate | 256 Samples/Cycle |
| Voltage Harmonics (Individual, Even, Odd, Total) Up to – | 511Th |
| Current Harmonics (Individual, Even, Odd, Total) Up to – | 127Th |
| Type of Analog to Digital Converter | 16/201 bit |
Storage Capacity | |
| Internal Memory | 32 GB/32TB2 |
Power Quality Analysis | |
| transient Detection, Microseconds (50Hz/60Hz) | 19.5/16.3μs |
Communication Ports | |
| Ethernet Ports | 3 |
| Wi-Fi Communications (802.11g) | 1 |
| Power Over Ethernet (PoE- Out) | 1 |
| Digital Input | 4 |
| RS-232 | 1 |
| RS-485 | 1 |
Physical | |
| Dimensions mm | 314 X 84 X 271 |
| Weight | 3.7kg |
Control | |
| Comprehensive web server for local and remote real-time monitoring and control | |
Applicable Standards | |
| Measurement Standards | EN50160, IEEE1159, IEEE519, IEC61000-4-15, IEC61000-4-7, IEC61000-4-30 Class A EMC Standards EN61326, CFR47FCC, CISPR11 Group 1, FCC PART 15 Subpart B, EN61010-2, IEC61000-3-3, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-11 |
| Environmental Standards | IEC60068-2-1, 2, 6, 27, 30, 75 |
| Safety Standards | EN61010-1:2001 2nd Edition |
Power Supply | |
| Operating Range | 100-260 VAC: 50/60 Hz 100-300 VDC |
| Auxiliary DC Supply | 48 VDC |
| Auxiliary Supply | PoE In According to 802.3af |
| Battery Backup | 2 Hours |
Environmental Conditions | |
| Operation Temperature | 0°C – 50°C (32°F – 122 °F) |
| Storage Temperature | -20°C – 60°C (-4°F – 140 °F) |
Time Synchronization | |
| Real Time Clock | ±1 Second per 24 Hours |
| GPS | 100-200μs |
| IRIG B | 100-200μs |
| SNTP Server | 50-100μs |
| DCF-77 | ±15ms |
Voltage Channels | |
| Voltage Channels | 4 (3 Phases + Neut.)+ 1 DC |
| Nominal Full Scale | 1000V |
| Maximum Peak Measurement | 8000V |
| Input Impedance | 3MΩ |
| Uncertainty | 0.1% of Nominal |
Current Channels | |
| Current Channels | 4 (3 Phases + Neut.)+ 1Grn/DC |
| Current Channels Receive From Clamp | I1-I4: 0-10 VPk I5: 0-3 VPk |
| Uncertainty | 0.1% ±0.1 mV |
Frequency Measurement | |
| Fundamental Frequency | 42.5 Hz to 69 Hz |
| Frequency Resolution | 10 mHz |
| Frequency Accuracy | ±10 mHz |
| Ordering Information | SOA-0010-0500 |
| Measurement Range | 6/60AAC |
| Output Signal | 100m V/A |
| Operating Temperature | – 20°C to + 60°C |
| Cable Length | 1.2m |

| Ordering Information | SOA-0270-14001 |
| Measurement Range | 1,500A DC / 1,000A AC |
| Output Signal | 1m V/A, 10m V/A |
| Operating Temperature | – 10°C to + 55°C |
| Cable Length | 1.4m |

| Ordering Information | SOA-0180-5000 |
| “Hole” Dimensions | 10mm Max |
| Measurement Range | Up to 100APK AC |
| Output Signal | 100m V/A |
| Operating Temperature | – 20°C to + 60°C |
| Cable Length | 1.2m |

| Ordering Information | SOA-3003-0270 |
| Measurement Range | 30A/300A/3000A AC RMS |
| Operating Temperature | – 20°C to + 65°C |
| Probe Cable Length | 610mm (24”) |
| Probe Cable Diameter | 194mm (7.5”) |

| Ordering Information | SOA-9045-3001 |
| Measurement Range | 90A – 4,200A |
| Operating Temperature | – 20°C to + 60°C |
| Cable Length | 2m |
| Probe Length | 80cm |

| Ordering Information | SOA-9091-3000 |
| Measurement Range | 9A – 1,050A |
| Operating Temperature | – 20°C to + 60°C |
| Cable Length | 2m |
| Probe Length | 45cm |

The GPS provides an optimal mobile time synchronization solution for accurate time data via satellite signal. In absence of any other available technologies, it synchronizes the time at any remote location.